Raychem Wintergard System
The Wintergard system, comprising of FS-A-2X, FS-B-2X & FS-C-2X is a legacy system which has been superseded by the XL-Trace system.
The FS-C10-2X cable is still available to protect hot water systems.
We do have limited stocks available to extend existing installs, or for small new installs, however for new larger installs it is suggested to use the newer XL-Trace system.
The products below are shown for historical / legacy reasons but limited stock of some are still available.
The Raychem Wintergard products shown are suitable for any pipe material (copper, threaded pipes, stainless steel pipes, plastic pipes and composite metal pipes) without restriction by using the appropriate fixing tape to attach the cable to the pipework.
Connection of the cable is using the Raychem Rayclic system.
FS-A-2X
Raychem Part Number: 277783-000
Raychem’s FS-A-2X is a self-regulating frost protection cable rated at 10W/m at 5°C. A typical use would be to protect pipework where the operating temperature does not exceed 65°C.
Suitable for pipes up to 108mm/4” diameter (depending on insulation thickness and temperature)
FS-B-2X
Raychem Part Number: 976819-000
Raychem’s FS-B-2X is a self-regulating frost protection cable rated at 26W/m at 5°C. A typical use would be to protect pipework where the operating temperature does not exceed 65°C.
Suitable for pipes between 22mm/¾” and 200mm/8” diameter.
FS-C-2X
Raychem Part Number: 067007-000
Self-regulating frost protection cable 31W/m at 5°C or 22W/m at 40°C.
This cable is used for frost protection of pipework up to a maximum operating temperature of 95°C. It is also used for temperature maintenance of metal waste pipes with fatty waste water and for snow melting of metal fire escapes with solid treads.