Raychem SBS-xx-SNR Control Panels

SBS-xx-SNR Control Panel Image

The SBS-xx-SNR control panel for pipe frost protection of sprinkler systems provides a totally integrated solution for the control of Raychem self-regulating heating cables for sprinkler applications.

The control panel comprises multi-control and multi-sensor thermostatic control and redundant circuit automatic switching capability in order to be compliant with the requirements of BS EN12845:2008.

The SBS-xx-SNR panels can switch 2-12 circuits of frost protection heating cables with up to 12 control and sensor inputs (one per primary circuit and one redundant circuit). The panel also includes electrical circuit protection devices (C-type circuit breakers and RCD protection) for safety and peace of mind.

The panels need only be connected to the 230Vac or 400VAC (Three Phase) power supply.

Benefits

  • Increased safety through automatically switching redundant (Back up) heating circuit
  • All trace heating circuit protection built-in; no need for additional heater circuit protection devices.
  • EN60204-1 and EN60439-1 compliant multi-circuit control panels
  • Robust metal enclosure (RAL7035 – light Grey) housing with IP54 rating.

Available Products

Product CodeDescriptionRaychem Part Number
SBS-02-SNRControl panel for 2 heating circuits (inc. redundant)185780-000
SBS-04-SNRControl panel for 4 heating circuits (inc. redundant)278362-000
SBS-06-SNRControl panel for 6 heating circuits (inc. redundant)300074-000
SBS-08-SNRControl panel for 8 heating circuits (inc. redundant)158834-000
SBS-10-SNRControl panel for 10 heating circuits (inc. redundant)012276-000
SBS-12-SNRControl panel for 12 heating circuits (inc. redundant)712998-000
Control Type2 x Elreha Tarn 1170 Digital control per sprinkler pipe:
  1. Prime circuit.
  2. Redundant circuit. (Max. 12 controllers per panel).
Supply Voltage400 Vac / 230 Vac 50/60Hztd>
Temperature setpoint8°C prime heater circuit switch-on 5°C redundant (back-up) circuit switch-ontd>
ApprovalCE (Approved to IEC 60204-1 and IEC60439-1). Built to support requirements of EN12845td>
Heater circuit breaker size16A per heating circuit.
Installation locationIndoors (IP 54)
Selector SwitchPrime circuit / Redundant Circuit / Off